Tengah Vines Common Defects 

When mulling over the specifics of a rectification request (that you are accomplishing by yourself or with a private defect check contractor), this real-life case on a Tengah Vines BTO project might come handy. Read through the following defects that were discovered during the inspection.

Improper Installation of the Centralized Air Conditioning System

Take this indoor component of a centralized split-type air conditioning unit inside the Tengah Vines’ flat, for example, and note its improper installation. Pay attention to the lack of wall brackets to support and stabilize the equipment as well as the uneven placement: there is a visible gap between the AC and the wall. Moreover, the hacking of the wall for the air conditioner’s wiring and piping network is not well concealed–an unsafe configuration all in all. As for the surface-level defects, note the patchy paintwork on the aircon trunking which protects and hides the piping.

Flooring Defect and Sunken Vinyl

Here, the Tengah Vines’ BTO flat, shows a flooring defect uncovered through competent inspection and practical testing techniques. By applying sudden pressure against the vinyl flooring, you will see (and even hear) the improperly sealed contact area between the vinyl and the cement; there is a gap that you can detect by simply pressing against the flooring. 

The Building and Construction Authority (BCA) allows a limit of 2mm for a contact area gap. If you can barely hear and feel the gap, that means it’s usually okay. If the whole room, however, is giving out that tell-tale hollow sound when you test the floor, it means the vinyl is mostly sunken. This rectification normally takes the longest to be addressed, compared to the other BTO defects. But, a ‘sunken vinyl’ issue may not apply to you if you are going to renovate your flooring. 

Flaws on Electrical Sockets

Some of the electrical sockets at the Tengah Vines’ BTO flat have been discovered to be improperly wired. The ‘earth’ and ‘live’ wirings were mixed up, which renders the power socket totally unusable and hazardous. Plugging something into the improperly wired socket will lead to trippage, or worse–an electrical spark which could start a fire. This article, “Top Three Wall Socket Defects To Check in Your New BTO Unit,” provides more useful information that can assist you during your home inspection.

Window Defects

The window glass was also found to be flawed. As you can see in the above photo, a rounded distortion appears. When looked through, the glass imposes an anomaly on the image. This can be corrected, if reported through a rectification request.

Skirting and Silicon Workmanship Issues

The flaws on the skirting are instantly obvious. They result from poor or hasty workmanship. The silicon and skirting are also not properly sealed–and this is something you must pay close attention to.

Defects in the Toilet

A showerhead check reveals a leak. There’s also congestion and choking in the basin’s overflow hole. Plus, there are defects in the tiling pointing. All these flaws in the toilet construction and fixtures, if you know where to look and how to check them, can be included in your rectification request. 

Conclusion

The Tengah Vines’ BTO project has a higher-than-usual amount of defects due to the inclusion of a centralized cooling system. Other workmanship defects, such as wall paint and skirting/silicon defects, are already commonly found in most BTO flats.